BY NYC Energy Code Team ON 29 November 2026

NYC Energy Code Documentation Checklist: What Must Be Included in Construction Plans

Architect reviewing NYC Energy Conservation Code construction plans and building compliance documents Architect reviewing NYC Energy Conservation Code construction plans, Supporting Documentation Indexes, and energy compliance drawings inside a New York City commercial project.

A practical guide to preparing 2025 NYC Energy Conservation Code construction documents, including energy analysis, architectural and MEP drawings, supporting documentation indexes, TR8 inspections, commissioning statements, and final DOB sign-off requirements.

Introduction: Why NYC Energy Code Documentation Matters

Preparing construction plans for a New York City building project involves more than submitting architectural drawings and engineering calculations. Building owners, developers, architects, and engineers must demonstrate that their proposed construction meets the applicable New York City Energy Conservation Code (NYCECC).

The Department of Buildings (DOB) requires supporting documentation that connects the proposed design to specific energy efficiency requirements. Under the 2025 NYCECC (enforced starting March 30, 2026), projects must account for updated rules covering building envelopes, HVAC systems, lighting, energy efficiency credits, air leakage testing, and additional construction documentation.

A typical energy code submission includes:

  • Professional Statement and Energy Analysis.
  • Supporting Documentation Index linking code sections to drawing sheets.
  • Architectural & Building Envelope Details (insulation, fenestration, thermal bridges, air barriers).
  • Mechanical, Service Water Heating & Electrical Schedules.
  • Energy Efficiency Credit Calculations (C406 / R408), TR8 Inspections, and Commissioning.

Missing or inconsistent documents can trigger DOB objections, redesign work, and construction delays. This guide breaks down every document required in NYC energy code construction plans.

1. Understand Which NYC Energy Code Applies to Your Project

Adopted through Local Law 47 of 2026, the 2025 NYCECC incorporates the 2025 New York State Energy Conservation Construction Code (2024 IECC and ASHRAE 90.1-2022 framework) with NYC modifications.

Application Status Applicable Energy Code
Complete application filed on or before March 29, 2026 Generally 2020 NYCECC
Complete application filed on or after March 30, 2026 2025 NYCECC
Incomplete application filed before March 30, 2026 May be subject to 2025 NYCECC
Material post-approval design change May trigger updated energy code requirements

Residential projects generally follow Chapters R2–R6, commercial projects follow Chapters C2–C6 or modified 2025 NYC ASHRAE 90.1, and qualifying mixed-occupancy buildings (three stories or fewer) may require separate residential and commercial analyses.

2. Understand the NYC DOB Energy Submission Structure

For new buildings and major alterations, DOB separates the Energy (EN) Plan Set from the main trade drawing filings and reviews them in parallel. Final approval of the main filing depends on EN Plan Set approval.

Submission Filing Typical Documents Included
GC / Architectural Floor plans, elevations, wall sections, window schedules, roof details, envelope assemblies
MS / Mechanical HVAC equipment, ventilation, ductwork, controls, mechanical schedules
PL / Plumbing Service water heating equipment, hot water distribution, piping and insulation
Electrical Lighting layouts, fixtures, controls, power, electrical metering and monitoring
EN / Energy Energy Analysis, Professional Statement, Supporting Documentation Index, TR8, commissioning & calculations

3. Professional Statement & Energy Analysis

Every applicable application must include a signed and sealed Professional Statement identifying the project address, code edition, compliance pathway, and compliance or specific code exemption.

The Energy Analysis demonstrates compliance using one of four accepted formats:

Analysis Method Required Documentation
Tabular Analysis Code values, proposed values, code references, and supporting drawing locations
REScheck (2025 NYC Version) Full 2025 NYC report (generic IECC REScheck is not accepted)
COMcheck (2025 NYC Version) Correct 2025 NYCECC or modified 2025 NYC ASHRAE 90.1 report
Whole-Building Energy Modeling EN1 form, proposed & baseline model reports, modeling narrative, and unmet load hour checks

4. Supporting Documentation Index

The Supporting Documentation Index bridges the Energy Analysis and construction drawings so DOB reviewers and progress inspectors can trace every proposed value directly to a drawing sheet or schedule.

Code Reference Item Proposed Design Value Supporting Document
C402 Roof & Wall Insulation Project-specific R-value A-401 Roof / A-501 Wall Section
C402 Window Performance U-factor and SHGC A-601 Window Schedule
C403 HVAC Equipment Capacity and efficiency M-301 Equipment Schedule
C404 Service Water Heating Equipment performance P-201 Plumbing Schedule
C405 Interior Lighting & Controls LPD & occupancy/daylight controls E-301 Lighting / E-302 Controls
C406 Additional Efficiency Credits Calculated credit value EN-101 Credit Summary

5. Architectural and Building Envelope Drawings

Infographic showing architectural, mechanical, electrical, energy analysis, and inspection documentation for NYC Energy Code compliance
Figure 1: Core documentation packages integrated into the NYC DOB Energy Submission process.

Architectural plans must detail every exterior wall, roof, foundation, and slab assembly, continuous insulation R-values, U-factors, fenestration schedules (U-factor, SHGC, VT, air leakage, and commercial fenestration below the 95-foot reference line), linear/point thermal bridge mitigation, and a continuous Air Barrier Continuity Plan.

6. Mechanical, Plumbing, and Electrical Drawings

  • Mechanical & Plumbing (MS / PL): Complete HVAC equipment schedules (showing total installed heating, cooling, and service water heating capacity), outdoor air and exhaust ventilation designs, duct/pipe insulation, economizer/ERV details, and detailed control narratives (generic notes like "automatic controls shall be provided" are rejected).
  • Electrical & Lighting: Fixture schedules, watts per fixture, Lighting Power Density (LPD) calculations, occupancy/daylight control diagrams, motor horsepower/VFDs, whole-building/tenant submetering locations, EV readiness, and permanent energy certificate requirements.

7. Additional Energy Credits, TR8 Inspections & Air Leakage Testing

Under the 2025 NYCECC, qualifying projects must include an Energy Credit Summary Table (C406, C502.3.7, C503.6, or R408) linking each selected credit measure to drawing sheets and specifications.

NYC building inspector reviewing energy code construction drawings and building envelope compliance
Figure 2: Progress inspector verifying air barrier continuity and insulation assembly details against approved EN construction plans.
  • TR8 Progress Inspections: Construction drawings must explicitly list all applicable TR8 inspection items (envelope insulation, air barrier, fenestration, HVAC controls, lighting, metering, and air leakage testing) so contractors do not enclose work prematurely.
  • Air Leakage Testing: New construction requires blower door testing—with commercial Section C402.6.2 capping whole-building leakage at 0.35 cfm/sq. ft. at 75 Pascals, verified by an approved independent third-party tester.
  • Commissioning (Section C408): Required unless the project has both less than 10,000 sq. ft. of conditioned floor area and combined heating, cooling, and service water heating capacity below 960,000 Btu/h. Owners must receive O&M manuals and balancing reports within 90 days of CO or Letter of Completion.

8. Final Energy Code Sign-Off (TR8 & EN2)

Before final DOB sign-off, the progress inspector must sign and seal the final TR8 certifying all inspections passed, and both the applicant and progress inspector must complete the EN2 confirming that installed conditions match the approved (or revised as-built) Energy Analysis.

9. Master NYC Energy Code Documentation Checklist

Document / Drawing Main Information Required Typical Responsibility
Professional Statement & Energy Analysis Code path, proposed values & compliance software report Registered Design Professional
Supporting Documentation Index Code reference and drawing location for each item Design Team
Architectural & Envelope Details Insulation, air barriers, windows & thermal bridges Architect / Envelope Consultant
Mechanical, Plumbing & Electrical HVAC, DHW, lighting power, controls & metering MEP Engineers
TR8, Air Leakage & Commissioning Progress inspection table, blower door plan & C408 plan Design Team & Cx Provider
Final TR8 & EN2 Completed inspection certification & as-built conformance Applicant & Progress Inspector

10. Common Reasons Submissions Receive Objections

  • Mismatched Values: Energy Analysis R-values, U-factors, or HVAC efficiencies conflict with architectural or MEP schedules.
  • Missing Supporting References: Proposed values lack sheet citations in the Supporting Documentation Index.
  • Generic Control Notes: Omitting explicit HVAC and lighting control sequences and setpoints.
  • Missing C406 Credits or Air Barrier Plans: Claiming credits without calculations or specifying blower door testing without an air barrier continuity diagram.
  • Unreported Field Changes: Failing to file post-approval amendments and revised as-built Energy Analyses before EN2 sign-off.

Pre-Submission QA/QC Summary

Confirm the governing code edition (2020 vs. 2025 NYCECC), verify 2025 NYC-specific software reports, cross-check every Energy Analysis input against GC/MS/PL/EN sheets via the Supporting Documentation Index, and incorporate TR8, blower door testing, and C408 commissioning milestones into the project schedule before filing.

Frequently Asked Questions (FAQs)

The applicable submission generally includes a Professional Statement, Energy Analysis, Supporting Documentation Index, TR8 progress inspection information, relevant construction drawings, commissioning documentation where applicable, and required energy calculations and testing information.

Yes. For projects subject to the DOB Energy Submission process, EN Plan Sets are submitted separately from the main Plans/Sketch packages. The main trade filings contain the supporting architectural, mechanical, plumbing, and electrical construction documents, which are referenced through the Supporting Documentation Index.

It is a table connecting each energy code requirement with its proposed design value and the corresponding construction drawing, schedule, calculation, or specification. It helps DOB reviewers and progress inspectors verify that the approved design demonstrates compliance.

Yes, for applicable projects. The complete 2025 New York City version of REScheck must be submitted. The generic IECC version is not accepted as a substitute. Applicable envelope, HVAC, and service water heating information must be included.

COMcheck can be used for applicable commercial energy analysis. The version must correspond to the selected compliance pathway: 2025 NYCECC or modified 2025 NYC ASHRAE 90.1. The supporting construction documents must also substantiate the values in the report.

TR8 certifies that required energy progress inspections have been completed and that inspected construction matches approved drawings. EN2 certifies that the actual installed energy values match the approved or properly revised as-built Energy Analysis.

Yes, the 2025 NYCECC requires air leakage testing for new construction. The applicable test method and criteria depend on whether the project follows residential, commercial, or modified ASHRAE 90.1 provisions.

It is supporting documentation identifying the additional efficiency measures selected to meet applicable 2025 NYCECC credit requirements. It should show the relevant code provision, credit calculation, technical evidence, and drawing locations.

No. Commissioning applies when the relevant code provisions are triggered and the project's systems fall within their scope. Certain smaller buildings meeting both the applicable floor-area and combined equipment-capacity conditions are exempt under DOB's stated C408 guidance.

The applicant must evaluate and document the changes. Where regulated energy values change, revised construction drawings and an updated, professionally certified as-built Energy Analysis may be required. The applicable EN2 sign-off must reflect the actual constructed conditions.

Related Articles